Tie-down Vector Dynamics Foundation System for Wind Zones I Manuale Utente Pagina 7

  • Scaricare
  • Aggiungi ai miei manuali
  • Stampa
  • Pagina
    / 19
  • Indice
  • SEGNALIBRI
  • Valutato. / 5. Basato su recensioni clienti
Vedere la pagina 6
Page 7 4/3/2013
50 in.
max.
Figure 1
50 in.
max.
24”
26” Maximum
Unequal Pier Heights
Homeswithunequalpierheightsarelimitedto50”maximumpierheight.Thedifferencebetweenthetallerpier
andtheshorterpiercannotexceed26”.
Figure 2
Maximum Pier Height
Vector Dynamics Foundation Systems may be used on single section homes in Wind Zone I which require pier
heights(fromsurfaceofVectorpadstotopofconcreteormetalpier)nottoexceed50inchesunderoneor
bothmainrail(s).NotethatagroundanchormustbeusedateachVectorsystemlocationwherethepierheight
exceeds 24 inches for single section homes. On multi-section homes in Wind Zone I, an anchor must be used at
eachVectorSystemlocationwithpierheightsabove46”withthefollowingexception:doublesectionhomesthat
are24’wide,inWindZoneI,haveamaximumpierheightwithoutanchorsof38”.Seepage13fordouble
section home high pier set instructions.
Vedere la pagina 6
1 2 3 4 5 6 7 8 9 10 11 12 ... 18 19

Commenti su questo manuale

Nessun commento