D1030
Tie Down Engineering
255 Villanova Drive SW
Atlanta, Georgia 30336
(404) 344-0000 • Fax (404) 349-0401
www.tiedown.com
Example of a Double Section 28' x 72' Home
Longitudinal (LSD)
Longitudinal (LSD)
Vector Systems
Anchors
Wind Zone II
WIND ZONE II for Double Section Homes
Using Vector Dynamics Foundation Systems
Home Length Vector Systems Anchors Required Longitudinal
Required Per Side Systems
1
(LSD)
0 to 48’ 4 4 2(4Struts)
49’ to 60’ 5 5 2(4Struts)
61’ to 72’ 6 6 2(4Struts)
73’ to 84’ 7 7 2(4Struts)
85’ to 90’ 8 8 2(4Struts)
NOTES:
Vector Systems should be spaced as symmetrical as
possible along the length of the home. Pier spacing must be
consistent with home manufacturers instruction and/or state
requirements.
Maximumallowable working load for metal strut: 3150 lbs.
1
One Longitudinal Vector System is made up of 2
struts, which can be used separately.
Soil Classifications: 2, 3, 4A & 4B
Soil Bearing Capacity: 1,000 PSF Minimum
Anchors Required: 30"with2-4"helixanchors(#59095)with1-1/4"Vertical Ties
19 Revised: 8/19/08